In this short podcast episode, Bryan talks about the placement of the TXV sensing bulb. He also explains how it affects the opening force on the TXV.
The TXV sensing bulb (or sensor on an EEV) provides the opening force for the valve. The warmer the bulb gets, the more the valve opens; the colder the bulb gets, the more the valve closes. The TXV also has a closing force provided by the spring pressure and equalizer (usually the external equalizer).
So, if you have a bulb that has been poorly mounted or insulated, you tend to have more opening force than the design. Your suction line will generally be colder than the airstream around the evaporator coil. If the sensing bulb has poor contact with the suction line, it will likely read warmer temperatures than it should.
When the TXV opens more than it should, the valve loses control and could lead to flooded conditions. (If that liquid gets to the compressor, then you could get catastrophic damage.) Generally speaking, improper TXV bulb placement will result in low superheat and potential flooding. When you have a high superheat or a starved evaporator, the sensing bulb placement is rarely the actual problem.
When mounting a sensing bulb, the suction line should be clean. Get rid of all Armaflex residue and ensure that the bulb is also clean. In some cases, you may need to insulate the bulb. You must also ensure that you mount the sensing bulb securely near the evaporator outlet, and you can be a few inches downstream of the external equalizer. Another common suggestion is to place the bulb on top of the line if the line is smaller than 7/8" (larger than 7/8", you can mount the bulb at 4 o'clock or 5 o'clock on the line).
Learn more about Refrigeration Technologies HERE.
If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.
More from HVAC School - For Techs, By Techs
Relative humidity is the number most technicians and homeowners know, but it can mislead. In this symposium session, Tim De Stasio and Sophie Ashley make the case that HVAC professionals should think…
In this short podcast episode, Bryan talks about why you're not done with a furnace service call or installation just because it lit. Ignition is just one part of the furnace sequence of operations, a…
In this session from the 2026 HVACR Training Symposium, Jim Fultz walks through his HVAC 101 class to help techs get through any gas furnace call. Jim's core message is to start with your senses, not…
In this short podcast episode, Bryan explains why every HVAC company needs a home performance contractor (or at least access to the skills provided by home performance contractors). Many people try to…
Heat pumps may be everywhere, but according to David Richardson, the industry is in danger of aiming at the wrong target. In this 2026 HVACR Training Symposium session, the Kentucky contractor's son,…