Short #39 - Tricky Amperages
About this episode
We talk about measuring tricky amperage on a blower and condensing fan motor. We also cover why you may be measuring inaccurately, resulting in a misdiagnosis.
When measuring amperage on a PSC blower motor, you may have noticed that amperage on the common is higher when the panel is off. Conversely, on ECM or X13 motors, the amperage is generally lower with the panel off. When measuring amperage, we recommend using a Bluetooth ammeter to take readings without letting the panels interfere with your measurements.
Anytime the amperage is low, the more difficulty the ammeter will have in measuring an accurate value. In cases where you're dealing with a very low amperage, you will need a higher-resolution ammeter for accurate measurements. One old-school way that you can increase your resolution is by using the 10-wrap method and putting that in series. Then, you take the amperage measurement and divide it by 10.
We don't recommend doing the under-load test on a blower; a bench test is much safer. However, the compressor and condenser fan motor capacitance can be measured under load. Outdoor tests can be a bit challenging because there is a greater possibility for interference. Current drawn outside of the clamps can indeed affect the reading, and several other nearby conductors draw current inside condensing units.
Sometimes, technicians replace perfectly fine run capacitors because the amperage seemed too high on an under-load test. To avoid interference, perform a bench test and check the actual microfarads. Tricky amperage interference also leads techs to condemn condenser fan motors when they really just picked up amperage outside the clamp. So, keep in mind that your meter could be running high or picking up interference. Any possible fail parts should undergo further testing to confirm that there's something wrong.
Learn more about Refrigeration Technologies HERE.
If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.
More from HVAC School - For Techs, By Techs
Relative humidity is the number most technicians and homeowners know, but it can mislead. In this symposium session, Tim De Stasio and Sophie Ashley make the case that HVAC professionals should think…
In this short podcast episode, Bryan talks about why you're not done with a furnace service call or installation just because it lit. Ignition is just one part of the furnace sequence of operations, a…
In this session from the 2026 HVACR Training Symposium, Jim Fultz walks through his HVAC 101 class to help techs get through any gas furnace call. Jim's core message is to start with your senses, not…
In this short podcast episode, Bryan explains why every HVAC company needs a home performance contractor (or at least access to the skills provided by home performance contractors). Many people try to…
Heat pumps may be everywhere, but according to David Richardson, the industry is in danger of aiming at the wrong target. In this 2026 HVACR Training Symposium session, the Kentucky contractor's son,…