In this short podcast episode, Bryan compares internal and externally equalized valves. He also covers how forces act upon the TXV.
Equalization does not happen on the off cycle. When we talk about equalization, we are merely talking about a force that balances against the bulb force. A TXV sets the superheat within an operating range at the evaporator outlet; the sensing bulb on the TXV detects temperature and pressure at the evaporator outlet. So, those readings apply an opening force to the bulb. (Think of this process as being quite similar to you measuring the superheat and suction pressure.)
The equalizing force is a closing force. When the closing force is applied to the TXV, it balances against the opening force provided by the sensing bulb. So, we have two ways of providing the closing force: within the valve at the evaporator inlet (internal) or externally.
In an internally equalized TXV, the closing force that equalizes the bulb's opening pressure is taken at the evaporator inlet. The measurement is internal to the valve at the evaporator inlet. However, in externally equalized valves, the closing force comes from the evaporator outlet, which is beyond the valve. Externally equalized valves work best on systems with significant pressure drops within the evaporator coil or on systems with distributors. If we were to use internally equalized TXVs in those cases, it would be like measuring superheat at the wrong location.
If you don't have a significant pressure drop, then you can use an internally equalized valve. These systems will usually be small (less than one ton) and won't have distributors. Most of the time, we will see externally equalized TXVs; these will ideally take readings within six inches of the bulb.
Learn more about Refrigeration Technologies HERE.
If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.
More from HVAC School - For Techs, By Techs
Relative humidity is the number most technicians and homeowners know, but it can mislead. In this symposium session, Tim De Stasio and Sophie Ashley make the case that HVAC professionals should think…
In this short podcast episode, Bryan talks about why you're not done with a furnace service call or installation just because it lit. Ignition is just one part of the furnace sequence of operations, a…
In this session from the 2026 HVACR Training Symposium, Jim Fultz walks through his HVAC 101 class to help techs get through any gas furnace call. Jim's core message is to start with your senses, not…
In this short podcast episode, Bryan explains why every HVAC company needs a home performance contractor (or at least access to the skills provided by home performance contractors). Many people try to…
Heat pumps may be everywhere, but according to David Richardson, the industry is in danger of aiming at the wrong target. In this 2026 HVACR Training Symposium session, the Kentucky contractor's son,…