Demand Cooling + Liquid and Vapor Injection
About this episode
Trevor Matthews is back and dropping more compressor knowledge on us. This time, he talks about demand cooling and liquid and vapor injection.
In low-temperature applications, the discharge temperature would get very high and lead to oil breakdown and thermal overload, so demand cooling is a means of cooling the compressor. Demand cooling injects saturated refrigerant into the compressor body to cool it down. You're not jamming liquid into the compressor; the refrigerant flashes, which achieves a cooling effect.
A demand cooling system consists of a module, temperature probe, liquid line solenoid valve, and injection valve. On the Discus compressors, the sensor will go in the port in the compressor head. When installing these, it is important to make sure high-quality goes to the valve. It's normal to have some frost at the outlet during operation; look for frost to make sure the demand cooling system is working properly.
Scroll compressors use liquid and vapor injection almost exclusively nowadays. However, there is a difference between liquid and vapor injection for scroll compressors. A liquid injection system helps the compressor avoid high discharge temperatures (and high compression ratios). The vapor injection improves capacity and efficiency.
When troubleshooting demand cooling or liquid/vapor injection systems, you need to keep a few things in mind. For example, you need to make sure you have the right amount of tees when you retrofit a compressor with a vapor injection system. You may also have to repipe the vapor line and add a DTC (discharge temperature control valves).
Trevor and Bryan also discuss:
- What happens when we change refrigerants
- Return gas temperature and mass flow rate
- Compressor head cooling fans
- Motor operation and spinning indicators
- Visual inspection
- Vapor injection vs. mechanical subcooling
- KVE vs. K4E
- Part replacement
- DTC vs. EEV w/ CoreSense diagnostics
Learn more about Refrigeration Technologies HERE.
If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.
More from HVAC School - For Techs, By Techs
Relative humidity is the number most technicians and homeowners know, but it can mislead. In this symposium session, Tim De Stasio and Sophie Ashley make the case that HVAC professionals should think…
In this short podcast episode, Bryan talks about why you're not done with a furnace service call or installation just because it lit. Ignition is just one part of the furnace sequence of operations, a…
In this session from the 2026 HVACR Training Symposium, Jim Fultz walks through his HVAC 101 class to help techs get through any gas furnace call. Jim's core message is to start with your senses, not…
In this short podcast episode, Bryan explains why every HVAC company needs a home performance contractor (or at least access to the skills provided by home performance contractors). Many people try to…
Heat pumps may be everywhere, but according to David Richardson, the industry is in danger of aiming at the wrong target. In this 2026 HVACR Training Symposium session, the Kentucky contractor's son,…