HVAC School - For Techs, By Techs
Compressor Overheating Diagnosis & Prevention

Compressor Overheating Diagnosis & Prevention

HVAC School - For Techs, By Techs

31:53

About this episode

In this podcast episode, Bryan and Eric Mele discuss the diagnosis and prevention of compressor overheating in HVAC and refrigeration.

The main causes of compressor overheating are inadequate cooling back to the compressor, low charge, restrictions, and sometimes even poor suction line insulation. We want to keep the suction temperature low while maintaining appropriate superheat. If the suction line temperature is too high, the compressor can't cool down well enough. Dirty condenser coils, low voltage, weak capacitors, or an inadequate condenser fan can also lead to compressor overheating.

Electrical problems, including too little capacitance, will make a compressor go out on thermal overload. When you have refrigerant problems, the thermal mass will just keep growing; it takes a long time to heat the compressor up, and it will take a long time to cool it down.

In a thermal overload, a bimetallic disk in the compressor will open and break all three legs of power. When a compressor goes out on thermal overload, it will make an open circuit, and you will read infinite ohms. Knowing that the compressor has gone out on thermal overload is just the beginning of compressor overheating diagnosis.

So, to begin diagnosis, you'll want to make sure there's refrigerant in the system. Inspect the unit visually and note anything that seems odd. Then, you'd check your capacitor for electrical problems. You can also feel the compressor to get an idea of the extent of the overheating (try not to burn yourself). You'll also want to monitor the amp draw, condensing temperature, suction pressure, and superheat.

Eric and Bryan also discuss:

  • Axial fans
  • Condenser fan intermittent failures
  • Resetting the compressor
  • Cooling down the compressor
  • Setting up your meter
  • Being out on high pressure
  • Wrapping wire to increase ammeter resolution
  • High return gas temperature
 

Learn more about Refrigeration Technologies HERE.

If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

More from HVAC School - For Techs, By Techs

Relative humidity is the number most technicians and homeowners know, but it can mislead. In this symposium session, Tim De Stasio and Sophie Ashley make the case that HVAC professionals should think…

1h 25m

In this short podcast episode, Bryan talks about why you're not done with a furnace service call or installation just because it lit. Ignition is just one part of the furnace sequence of operations, a…

13m

In this session from the 2026 HVACR Training Symposium, Jim Fultz walks through his HVAC 101 class to help techs get through any gas furnace call. Jim's core message is to start with your senses, not…

1h 8m