Check The Charge Without Connecting Gauges - Part 2
About this episode
In this second part of the podcast, Jim Bergmann wraps up the steps to check a system charge without connecting a gauge manifold.
You can check the charge without gauges if you use the following process (and know your DTD, CTOA, etc.):
- Take the dry-bulb temperature. (Let's say it's 70°F in this example.)
- Subtract the DTD (35°F).
- Add target superheat (10°F).
- Check the suction line. It should be 45°F in this example. If your probe senses a temperature that is NOT within 5°F of the temperature you calculated, check the filter, evaporator coil, etc., for dirt.
- If the system is not dirty, check the charge with gauges.
For a more extensive look at the process in writing, check out THIS article.
If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.
More from HVAC School - For Techs, By Techs
Relative humidity is the number most technicians and homeowners know, but it can mislead. In this symposium session, Tim De Stasio and Sophie Ashley make the case that HVAC professionals should think…
In this short podcast episode, Bryan talks about why you're not done with a furnace service call or installation just because it lit. Ignition is just one part of the furnace sequence of operations, a…
In this session from the 2026 HVACR Training Symposium, Jim Fultz walks through his HVAC 101 class to help techs get through any gas furnace call. Jim's core message is to start with your senses, not…
In this short podcast episode, Bryan explains why every HVAC company needs a home performance contractor (or at least access to the skills provided by home performance contractors). Many people try to…
Heat pumps may be everywhere, but according to David Richardson, the industry is in danger of aiming at the wrong target. In this 2026 HVACR Training Symposium session, the Kentucky contractor's son,…