Blends and Midpoint w/ Jim Bergmann
About this episode
Jim talks about dew point, bubble point, and midpoint in refrigerant blends. He also covers the purpose of each and why MeasureQuick displays midpoint on the gauges.
We've formerly used mostly pure refrigerants. However, as new refrigerant blends come on the scene, we have to deal with glide, which indicates that we have a range of boiling temperatures instead of a fixed boiling point. We have bubble point and dew point, which are when the refrigerant starts to boil and finishes boiling, respectively; you generally use dew point to determine the superheat and bubble point to determine the subcooling. Zeotropic refrigerants have larger glides than near-azeotropic refrigerant blends; azeotropes have no glide at all.
The midpoint is the halfway point between the bubble point and dew point in refrigerant blends. Coil temperature typically corresponds with the midpoint.
To find the midpoint of refrigerant in the condenser coil, add the dew and bubble points and divide the sum by two. The process is a bit trickier on evaporator coils. In the evaporator, you run refrigerant through the metering device and get some flash gas; when the refrigerant undergoes that change, the bubble and dew points change. As a result, the midpoint becomes a bit more weighted towards the dew point (60%).
In MeasureQuick, the temperature-pressure charts go a step above and beyond to give you the superheat, subcooling, and midpoint. The midpoint is the effective temperature of the evaporator coil, which is a critical piece of information in refrigeration systems where food products are at stake. You can also use the midpoint for coil DTD and TD.
Jim and Bryan also discuss:
- R-410A and near-azeotropic refrigerants
- Metering devices as reactive components
- Coil temperature misconceptions and uncertainty
- Pressure differentials and drops in the system
- Maintaining food quality in refrigeration
- MeasureQuick mathematical models and formulas
Learn more about Refrigeration Technologies HERE.
If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.
More from HVAC School - For Techs, By Techs
Relative humidity is the number most technicians and homeowners know, but it can mislead. In this symposium session, Tim De Stasio and Sophie Ashley make the case that HVAC professionals should think…
In this short podcast episode, Bryan talks about why you're not done with a furnace service call or installation just because it lit. Ignition is just one part of the furnace sequence of operations, a…
In this session from the 2026 HVACR Training Symposium, Jim Fultz walks through his HVAC 101 class to help techs get through any gas furnace call. Jim's core message is to start with your senses, not…
In this short podcast episode, Bryan explains why every HVAC company needs a home performance contractor (or at least access to the skills provided by home performance contractors). Many people try to…
Heat pumps may be everywhere, but according to David Richardson, the industry is in danger of aiming at the wrong target. In this 2026 HVACR Training Symposium session, the Kentucky contractor's son,…