In this second part of the podcast, Jim Bergmann wraps up the steps to check a system charge without connecting a gauge manifold.

You can check the charge without gauges if you use the following process (and know your DTD, CTOA, etc.):

1.  Take the dry-bulb temperature. (Let's say it's 70°F in this example.)
2.  Subtract the DTD (35°F).
3.  Add target superheat (10°F).
4.  Check the suction line. It should be 45°F in this example. If your probe senses a temperature that is NOT within 5°F of the temperature you calculated, check the filter, evaporator coil, etc., for dirt.
5.  If the system is not dirty, check the charge with gauges.

 

For a more extensive look at the process in writing, check out [ THIS](https://hvacrschool.com/checking-the-charge-without-gauges-our-process/) article.